Run 1 chiller only, 20.2 to 21.2 to 20.2 deg C Run 2 chiller at 19 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 Run 3 test perturbations sample time = 60 sec chiller at 19 deg C, heater bringing water to air temp F = 1.8 gpm, G = 7.2 mm Kpb = 0.5 Ti = 10 Td = 5 12:00 start 12:30 I12 = 5 S 1:30 F = 1.6 gpm 2:30 Tchiller = 19.3 deg C 3:30 gap = 25 mm 4:30 end Run 4 chiller at 19 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.45 Ti = 5 Td = 10 Run 5 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.55 Ti = 10 Td = 3 Run 6 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 Run 7 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 baseline: gap = 7.2 mm, I12 = 0 A, sample time = 60 sec 12:30 start 1:00 open gap to 25.0 mm 2:00 close gap to 7.2 mm 3:00 set I12 = 5 A 4:00 set I12 = 0 A 5:00 end Run 8 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 baseline: gap = 7.2 mm, I12 = 0 A, sample time = 60 sec 10:20 start 11:00 F = 1.6 gpm 12:00 F = 1.8 gpm 1:00 Tchiller = 20.0 deg C 2:00 Tchiller = 19.5 deg C 3:00 end Run 9 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 Run 10 chiller at 19.5 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 baseline: gap = 7.2 mm, I12 = 0 A, sample time = 60 sec 10:30 start 11:30 Tchiller = 19.0 deg C 12:30 Tchiller = 19.5 deg C 1:30 end Run 11 chiller at 19.0 deg C, heater bringing water to air temp F = 1.8 gpm Kpb = 0.5 Ti = 10 Td = 5 feedback on tube after heater added buffer tank